The process
Curing presses release rubber fume at opening. Hoods over the presses take the fume to a scrubber or filter, and the curing hall needs heavy ventilation for the heat.
The gas at the fan
Rubber fume from curing presses condenses as a tacky film. The fan is in the exhaust after a scrubber or filter, with a wheel that can be cleaned and a casing with access doors.
Selection for this duty
| Construction | Axial fans in weatherproof cowls, or supply and exhaust units with filters as the air quality requires |
| Density at the fan | At about 80°C the gas density is close to 1.00 kg/m³, 83% of standard air. Pressure developed and power drawn fall in the same ratio, so the selection is made at this density and the motor is checked at cold start. |
An axial fan in a weatherproof cowl mounted on an inclined or flat roof, exhausting hot air from the ridge of a factory shed. Client-stated blade types for the Roof Extractor in general: Axial.
Industries
Other fans in tyre curing presses
Roof Extractor in other processes
Information needed to select or quote
- Gas volume and temperature. Actual flow at the inlet, normal and upset temperature, moisture.
- Dust or pollutant. Inlet loading, particle size distribution, whether it is abrasive, sticky, hygroscopic or combustible; for gases, the species and concentration.
- Required outlet. The emission limit or clean gas concentration the unit must meet.
- Site. Available space and height, material of construction preferences, and how the collected material is to be discharged.