Induced Draft (ID) Fan for Garden and Green Waste Fired Boilers

The ID fan on a garden and green waste boiler moves a large, wet flue gas volume that changes with the season and the mix of leaves, grass and wood. Water vapour from the fuel, more than ash, sets the gas volume, and soil grit with traces of chloride decides the materials.

Send your duty pointCall +91 91766 67102
150 to 180°C after the air heaterGas temperature, normal
0.81 kg/m³Gas density at 165°C
Backward curvedBlade form

How garden and green waste fired boilers work

Garden and green waste boilers burn shredded tree trimmings, leaves, grass cuttings and park waste collected by municipalities and estates. The fuel is very variable: woody prunings may carry 30 to 40% moisture, fresh grass and leaves 50 to 65%, and the whole stream brings soil, grit and stray plastics. Calorific value is low, often 1,800 to 2,800 kcal/kg as fired. Most plants use a reciprocating or step grate that tolerates oversize and wet fuel, with a tall refractory-lined furnace and preheated undergrate air to dry the fuel on the first grate section. Flue gas passes the boiler, economiser and air heater, then a multiclone and a bag filter, sometimes with lime injection for acid gases, before the ID fan and chimney.

Where the ID fan sits

  1. Reciprocating grate furnace
  2. Boiler
  3. Economiser
  4. Air heater
  5. Multiclone
  6. Lime injection and bag filter
  7. ID fan
  8. Chimney

The fan sits after the bag filter, which also collects the lime and reaction products where dry sorbent injection is used. The furnace is kept at a steady suction of a few mmWC so that smoke does not escape from the feed hopper and grate seals when wet fuel flashes off steam. Total suction at the fan inlet includes the boiler, air heater, multiclone and a bag filter that may run at 150 to 200 mmWC on its own, giving 250 to 400 mmWC in all.

Gas at the ID fan

Gas temperature, normal150 to 180°C after the air heater
Maximum or upsetUp to 230°C with dry woody fuel at full fire
Dust at the fanLow after the bag filter, typically below 50 mg/Nm³; soil silica and fine lime
Moisture and dew pointWater vapour of 20 to 30% by volume with wet grass and leaves; water dew point 60 to 70°C
Corrosive speciesHCl from stray plastics and salted soil; acid condensate on any surface below about 130°C
Density at the design temperatureAbout 0.81 kg/m³ at 165°C, 68% of standard air. Pressure developed and power drawn scale with density, so the fan is selected at this condition and the motor is checked at the coldest operating or start-up condition.

ID Fan selection for garden and green waste fired boilers

Blade formBackward curved, with wear protection at the inlet edges for soil grit
Material of constructionMild steel casing with full insulation; impeller in high strength steel, with SS 316 or corrosion-resistant lining where HCl is significant
Drive and arrangementDirect coupled, arrangement 8
Bearings and coolingPedestal bearings outside the gas path with a cooling disc
Flow controlVariable speed drive on furnace pressure
Also specifiedCasing drain, sealed inspection door, and selection at the wettest seasonal fuel

What this ID fan has to cope with

Seasonal swing in gas volume

In the rainy season and after lawn mowing, grass and leaf content can double the fuel moisture. Each extra kilogram of water leaves as about 1.2 Nm³ of vapour, so the gas volume at the fan rises sharply while the steam output falls. A fan selected on the dry woody fuel runs out of capacity. The duty is set on the wettest blend, with speed control for the rest of the year.

Acid condensation at shutdown

Green waste brings chloride from plastics, road salt and soil. When the boiler stops, the casing cools through the water and acid dew point, and wet chloride deposits corrode mild steel and pit the impeller. Insulation, a casing drain, purging with dry air before shutdown and corrosion-resistant lining in the worst areas reduce the damage.

Soil grit and bag filter upsets

Soil and sand picked up with the waste are abrasive. Normally the bag filter catches them, but a burst bag or a bypass during start-up sends grit straight to the fan. Inlet edge protection and vibration monitoring that warns of a bag failure protect the impeller.

Energy and control

Green waste plants run continuously, but their output varies with fuel moisture far more than with steam demand. A variable speed ID fan holds furnace pressure without throttling, and saves most when the fuel is dry and the gas volume is low. Drying or storing green waste under cover for a few weeks before firing reduces moisture, steam lost to evaporation, and the gas volume the fan must handle.

ID fan and FD fan in garden and green waste fired boilers

ID fanFD fan
PositionAfter the bag filter, before the chimneyBefore the air heater, feeding the grate
What it handlesWet flue gas with soil grit and chlorideAmbient air from a dusty yard
Temperature at the fan150 to 180°C, up to 230°CAmbient
Main design concernSeasonal gas volume and acid condensationDrying air through a wet, patchy bed
ControlFurnace pressureSteam pressure and oxygen

See also the Forced Draft (FD) Fan for garden and green waste fired boilers.

Questions buyers ask

Why does the ID fan on a green waste boiler need to be larger than on a wood chip boiler?

Garden and green waste carries much more water, especially grass and leaves, and that water leaves the furnace as vapour. For the same steam output the flue gas volume can be 20 to 40% higher than with seasoned wood chips. The ID fan is sized on this wetter gas, so it is larger in volume for the same boiler rating.

What material is best for a green waste boiler ID fan?

Mild steel is acceptable where the gas stays well above its dew point and chloride is low. Where plastics and salted soil bring chloride, and the plant starts and stops often, an insulated casing and an impeller with stainless steel or corrosion-resistant lining in the wettest areas last much longer. The decision depends on fuel analysis and operating pattern.

How can I reduce ID fan load on a garden and green waste boiler?

Reduce the fuel moisture by stacking and covering the waste before firing, seal air leaks at the feed hopper, ash discharge and air heater, and keep the bag filter differential pressure in its normal range. A variable speed drive then lets the fan follow the lower gas volume rather than throttling against a damper.

Information needed to quote an ID fan for garden and green waste fired boilers

  1. Duty point. Gas volume in m³/h or Am³/h at the fan inlet and the static pressure the fan must develop, with the margin you want on each.
  2. Gas condition. Normal and maximum gas temperature at the fan, dust loading after the collector, moisture and any acid gases such as SO₂ or HCl.
  3. System. Boiler or furnace capacity and fuel, collector type and its pressure drop, and the existing fan curve or nameplate if this is a replacement.
  4. Mechanical. Drive arrangement, flow control (damper, inlet vanes or variable speed drive), rotation and discharge orientation, and a layout drawing or site photograph.
  5. Fuel mix. Proportion of grass, leaves and woody material by season, and the measured or expected moisture range.
  6. Acid gas treatment. Whether lime or sorbent is injected, and the bag filter design pressure drop.

Built and tested in Chennai

Adroit Fantech Engineers has designed and manufactured industrial fans at Ayanambakkam, Chennai since 2004. Each impeller, casing and shaft is built for the gas and temperature it will see, performance tested as per IS 4894 or BS 848 Part I, and balanced to grade G 6.3 or G 2.5 as per ISO 21940-11, with the records supplied with the fan. We also replace rotors and retrofit existing fans of any make.