Induced Draft (ID) Fan for Bagasse Dumping Grate Boilers

The ID fan on a bagasse dumping grate boiler often follows a wet scrubber, so it handles saturated, gritty gas, and it must also hold draft through the periodic dumping of grate sections loaded with ash and field sand. Wet gas, sand and dumping disturbances together decide its material and control.

Send your duty pointCall +91 91766 67102
60 to 75°C after a wet scrubber, or 150 to 180°C dryGas temperature, normal
1.03 kg/m³Gas density at 70°C
Radial or backward curvedBlade form

How bagasse dumping grate boilers work

Dumping grate bagasse boilers, typically 20 to 80 TPH, are common in Indian sugar mills. Bagasse is spread pneumatically over a stationary grate made of tilting sections. Fines burn in suspension; the rest burns on the grate, where ash and sand collect until a section is tilted to dump it, usually every few hours depending on cane cleanliness. Many older mills fitted wet scrubbers after mechanical collectors to meet emission limits, while newer units use ESPs. Air comes from an FD fan through an air heater to each section, with secondary and distributor air from separate fans.

Where the ID fan sits

  1. Dumping grate furnace
  2. Boiler bank
  3. Air heater
  4. Mechanical collector
  5. Wet scrubber
  6. ID fan
  7. Chimney

On a mill with a wet scrubber, the ID fan sits after the scrubber and its mist eliminator, handling gas saturated at about 60 to 75°C. On a mill with an ESP, it handles dry gas at about 150 to 180°C. Suction is typically 200 to 300 mmWC, with the scrubber adding a significant share. Each dump briefly increases ash and sand in the gas and changes furnace pressure.

Gas at the ID fan

Gas temperature, normal60 to 75°C after a wet scrubber, or 150 to 180°C dry
Maximum or upsetUp to 200°C if scrubber water fails
Dust at the fanWet sand and ash slurry droplets after a scrubber; surges after each dump
Moisture and dew pointSaturated gas with entrained droplets after the scrubber
Corrosive speciesScrubber water with dissolved ash; mildly acidic to alkaline depending on make-up water
Density at the design temperatureAbout 1.03 kg/m³ at 70°C, 86% of standard air. Pressure developed and power drawn scale with density, so the fan is selected at this condition and the motor is checked at the coldest operating or start-up condition.

ID Fan selection for bagasse dumping grate boilers

Blade formRadial or backward curved, self-cleaning shape against wet deposits
Material of constructionStainless steel or rubber-lined mild steel after a wet scrubber; mild steel with liners on dry ESP duty
Drive and arrangementDirect coupled, arrangement 8
Bearings and coolingPedestal bearings; shaft seal against wet gas
Flow controlVariable speed drive on furnace draft with fast response
Also specifiedCasing drains, wash connections and a design check at the dry scrubber-failure temperature

What this ID fan has to cope with

Mud build-up on blades

Droplets carrying ash and sand stick to the blades and harden. Build-up is rarely even, so the impeller goes out of balance within weeks. A good mist eliminator, blade shapes that shed deposits, water wash connections and a drain keep the fan running between stops.

Corrosion and erosion together

Wet sand slurry both corrodes and erodes mild steel faster than either would alone, because erosion keeps removing the protective rust layer. An unprotected mild steel impeller after a scrubber may last only part of a season. Rubber lining, or stainless steel with hard liners at the leading edge, gives the fan a full season of life.

Scrubber water failure

If scrubber water stops, the fan suddenly sees dry gas at 150 to 200°C. Rubber linings, shaft seals and bearings must survive this until the boiler trip acts. We check materials, lining grade and shaft cooling at the dry temperature, and recommend a low scrubber water flow interlock to the boiler trip.

Draft swings at dumping

Tilting a section loaded with bagasse ash and field sand disturbs furnace pressure, and fresh bagasse spread on the dumped section can flare. A slow damper lets the furnace go positive and flame escapes at the doors. A variable speed drive with fast draft response keeps the furnace negative through the dump.

Energy and control

Dumping grate boilers with wet scrubbers have high system resistance, so the ID fan is often the largest auxiliary motor. Replacing damper control with a variable speed drive, keeping the scrubber pressure drop at its design value, and cleaning the mist eliminator regularly bring the largest savings. Mills converting from scrubber to ESP should re-check the fan, since the new duty is hotter, drier and lower in resistance.

ID fan and FD fan in bagasse dumping grate boilers

ID fanFD fan
PositionAfter wet scrubber or ESPBefore the air heater
What it handlesSaturated gas with sand slurry, or dry gasAmbient air
Temperature at the fan60 to 75°C wet, 150 to 180°C dryAmbient, 25 to 45°C
Main design concernCorrosion, deposits, draft at dumpingPressure as sections close
ControlFurnace draft, fast responsePlenum pressure

See also the Forced Draft (FD) Fan for bagasse dumping grate boilers.

Questions buyers ask

What ID fan material is used after a wet scrubber on a bagasse boiler?

Stainless steel or rubber-lined mild steel is used, because the gas is saturated and carries wet ash and sand that corrode and erode plain mild steel quickly. The fan also needs casing drains, water wash connections and a design check at the higher dry temperature in case scrubber water fails during operation.

Why does the ID fan vibrate after a few weeks on a bagasse dumping grate boiler?

Wet ash and sand from the scrubber build up unevenly on the blades and harden. A better mist eliminator, regular water washing through fixed nozzles and blade shapes that shed deposits slow the build-up. Balancing restores the fan for a time, but it does not remove the cause, so the deposits return.

Can we change the ID fan when converting from wet scrubber to ESP?

Yes, and it is usually necessary. Gas at an ESP outlet is hotter and drier, at lower density, and the system resistance changes once the scrubber is removed. The existing fan may be the wrong size, speed and material for the new duty. We recalculate the duty for the new system before reusing or replacing the fan.

Information needed to quote an ID fan for bagasse dumping grate boilers

  1. Duty point. Gas volume in m³/h or Am³/h at the fan inlet and the static pressure the fan must develop, with the margin you want on each.
  2. Gas condition. Normal and maximum gas temperature at the fan, dust loading after the collector, moisture and any acid gases such as SO₂ or HCl.
  3. System. Boiler or furnace capacity and fuel, collector type and its pressure drop, and the existing fan curve or nameplate if this is a replacement.
  4. Mechanical. Drive arrangement, flow control (damper, inlet vanes or variable speed drive), rotation and discharge orientation, and a layout drawing or site photograph.
  5. Scrubber details. Type of scrubber, pressure drop, and whether a mist eliminator is fitted.
  6. Dumping cycle. Frequency of dumping and number of grate sections.

Built and tested in Chennai

Adroit Fantech Engineers has designed and manufactured industrial fans at Ayanambakkam, Chennai since 2004. Each impeller, casing and shaft is built for the gas and temperature it will see, performance tested as per IS 4894 or BS 848 Part I, and balanced to grade G 6.3 or G 2.5 as per ISO 21940-11, with the records supplied with the fan. We also replace rotors and retrofit existing fans of any make.

ID Fan for related applications

Industries

Services on this fan

ID Fan for bagasse dumping grate boilers: send us your duty point