Forced Draft (FD) Fan for Brass and Bronze Melting Furnaces

The FD fan on a fuel-fired brass or bronze melting furnace is the combustion air blower for the oil or gas burner. It handles clean ambient air at modest pressure. On induction furnaces there is no FD fan, since there is no combustion, so this page applies to crucible, rotary and reverberatory furnaces only.

Send your duty pointCall +91 91766 67102
Ambient, but often 40 to 55°C close to a melting furnaceAir temperature at the fan
1.09 kg/m³Air density at 50°C
Backward curved or radial bladeBlade form

How brass and bronze melting furnaces work

Brass and bronze are melted in coreless induction furnaces, oil or gas-fired crucible furnaces, or small rotary and reverberatory furnaces for scrap. Melting runs at about 950 to 1,150°C. Zinc boils at 907°C, so brass melting gives off dense white zinc oxide fume, with lead oxide from leaded alloys and smoke from oily turnings. Induction furnaces have no flue gas at all; the fume is captured by a hood or lip extraction. Fuel-fired furnaces add combustion products at 900 to 1,100°C. In both cases the gas is cooled by dilution air or a cooling duct, passed through a spark arrestor and a bag filter, and drawn out by the ID fan.

Where the FD fan sits

  1. Inlet screen
  2. FD (combustion air) fan
  3. Air control valve
  4. Burner
  5. Crucible or furnace chamber

The blower is usually mounted on or beside the furnace and connected to the burner through a short air line with a control valve. On a tilting crucible furnace it is mounted on the frame or connected through a flexible hose that follows the tilt. The pressure needed is modest, typically 150 to 400 mmWC, covering the valve and burner. Because the blower is so close to the furnace, the air it takes in is often hot and dusty.

Air at the FD fan

Air temperature at the fanAmbient, but often 40 to 55°C close to a melting furnace
DustFoundry dust and fume around the furnace
Pressure at the fan outletTypically 150 to 400 mmWC
TurndownHigh fire for melting, low fire for holding and between heats
Density at the design temperatureAbout 1.09 kg/m³ at 50°C, 91% of standard air. Pressure developed and power drawn scale with density, so the fan is selected at this condition and the motor is checked at the coldest operating or start-up condition.

FD Fan selection for brass and bronze melting furnaces

Blade formBackward curved or radial blade, depending on size and pressure
Material of constructionMild steel
Drive and arrangementDirect mounted on the motor shaft
Bearings and coolingMotor bearings; motor rated for high ambient temperature near the furnace
Flow controlLinked air and fuel valves with high-low or modulating control
Also specifiedInlet screen and inlet ducting from a cooler, cleaner area

What this FD fan has to cope with

Hot, dusty inlet air

A blower placed close to the furnace draws air at 50°C or more carrying zinc fume and foundry sand. The warm air is less dense, so mass flow drops, and the dust builds up on the impeller and screen. Taking the inlet from outside the melting bay through a short duct restores the duty and keeps the wheel clean.

Incomplete combustion and more fume

Too little air makes the flame smoky and adds soot to the zinc fume load on the bag filter; too much air oxidises the melt, raises zinc loss and wastes fuel. A blower with enough pressure margin and a proper linked or modulating ratio control keeps the flame correct through melting and holding.

Motor overheating

Motors beside melting furnaces run in high ambient heat and radiant heat from the open lid. Insulation ages quickly and thermal trips stop the burner mid-heat. A motor with a suitable temperature class and a heat shield, or a remote fan location with a longer air line, avoids these trips.

Energy and control

Crucible and small rotary furnaces cycle between high fire and holding many times a shift. Modulating ratio control saves both fuel and blower power compared with a fixed high fire setting. Where several small furnaces are being replaced by induction melting, the combustion air blowers are retired and the fume extraction system becomes the only fan duty.

ID fan and FD fan in brass and bronze melting furnaces

ID fanFD fan
PositionAfter the bag filter, before the stackOn or beside the furnace, feeding the burner
What it handlesZinc fume with room air or combustion gasAmbient air
Temperature at the fan80 to 130°CAmbient, often warm near the furnace
Main design concernFume capture at the hoodCorrect flame and clean inlet air
ControlDuct suction with hood dampersBurner ratio

See also the Induced Draft (ID) Fan for brass and bronze melting furnaces.

Questions buyers ask

Does an induction furnace for brass need an FD fan?

No. An induction furnace heats the metal electrically and has no burner, so there is no forced draft fan or combustion air blower. The only fan duty is the fume extraction fan that captures zinc and lead fume at the furnace mouth and draws it through the bag filter.

What pressure does a brass crucible furnace burner need?

Typically 150 to 400 mmWC at the blower outlet, depending on the burner type, the fuel and the length of the air line. The burner maker's data sheet gives the required air pressure at full firing; the blower is selected for that plus the valve and line losses, with a modest margin.

Why does my combustion air blower lose flow over time?

Usually because the impeller and inlet screen are coated with foundry dust and zinc fume drawn in from around the furnace, and because the air it takes in is hot. Cleaning the wheel and screen and moving the inlet to a clean, cool air source normally restores the original flow.

Information needed to quote an FD fan for brass and bronze melting furnaces

  1. Duty point. Combustion air quantity in m³/h or kg/h and the static pressure at the fan outlet, with the margins you want.
  2. Air condition. Site ambient temperature range and altitude, and whether the fan takes ambient air or air already heated.
  3. System. Boiler or furnace capacity and fuel, resistance of the air heater, windbox, grate or burner, and the existing fan curve or nameplate if this is a replacement.
  4. Mechanical. Drive arrangement, flow control (damper, inlet vanes or variable speed drive), noise limit, rotation and discharge orientation.
  5. Burner. Burner type, fuel and firing rate, and required air pressure.
  6. Furnace type. Crucible, rotary or reverberatory, and whether the burner moves with a tilting body.

Built and tested in Chennai

Adroit Fantech Engineers has designed and manufactured industrial fans at Ayanambakkam, Chennai since 2004. Each impeller, casing and shaft is built for the gas and temperature it will see, performance tested as per IS 4894 or BS 848 Part I, and balanced to grade G 6.3 or G 2.5 as per ISO 21940-11, with the records supplied with the fan. We also replace rotors and retrofit existing fans of any make.

FD Fan for related applications

Industries

Services on this fan

FD Fan for brass and bronze melting furnaces: send us your duty point

Flow, pressure, air temperature and the fuel are enough to start a selection.