The process
Acid pickling tanks are hooded and the fume drawn to a scrubber in PP-FRP. The fan is in the same material, after the scrubber and mist eliminator, with the motor outside the gas path.
The gas at the fan
Fume from pickling, acid handling or reactor vents, corrosive and often wet. PP-FRP, FRP or rubber lined construction, with the motor outside the gas path.
Selection for this duty
| Blade form | Backward curved or aerofoil for the best efficiency on clean gas |
| Material of construction | PP-FRP, FRP or MS rubber lined, with the motor outside the gas path |
| Drive and bearings | Direct coupled or belt driven; belt drive where the duty point may need tuning at site |
| Also specified | Casing drain at the lowest point |
| Density at the fan | At about 40°C the gas density is close to 1.13 kg/m³, 94% of standard air. Pressure developed and power drawn fall in the same ratio, so the selection is made at this density and the motor is checked at cold start. |
Moves air through a plant or building for fresh air supply, heat removal and fume dilution where the system is ducted. Low pressure, long hours, so efficiency and noise set the selection. Client-stated blade types for the Ventilation Fan in general: Backward inclined and forward curved.
Industries
Other fans in pickling and acid treatment lines
Ventilation Fan in other processes
Services on this fan
Information needed to select or quote
- Duty point. Volume flow and static pressure at the fan inlet, with the gas density and temperature or the conditions to derive it.
- Operating conditions. Site altitude, normal operating temperature and continuous or intermittent duty.
- Gas stream. Dust loading and particle size, corrosive species, moisture, upset temperature and any tendency of the material to deposit on the impeller.
- Mechanical. Rotation viewed from the drive end, discharge orientation and motor power.