Induced Draft (ID) Fan · designed and built in Chennai

Induced Draft (ID) Fan for Tobacco Redrying Plants

The ID fan on a tobacco redrying plant is the exhaust fan that draws moist air out of the apron redryer zones and the reordering section. It handles warm, humid air carrying tobacco dust and fine fibres, so dust shedding, condensation and fire risk decide the design more than the pressure.

Send your duty pointCall +91 91766 67102
50 to 80°C from the drying zonesAir temperature, normal
1.03 kg/m³Gas density at 70°C
Backward inclined flat bladeBlade form

How tobacco redrying plants work

In a green leaf threshing and redrying plant, cured tobacco is conditioned with steam and water, threshed to separate lamina from stem, and then redried to a uniform moisture for storage and ageing. Lamina and stems pass on separate lines through apron redryers: long, multi-zone conveyor dryers in which zone fans blow heated air up through the bed. The drying zones run at about 60 to 100°C, heated by steam coils from the plant boiler. Cooling zones then bring the leaf down with ambient air, and a reordering zone adds steam and water spray to bring it back to about 11 to 13% moisture before packing. Each zone has its circulation fan, and exhaust fans remove the moist air from the drying and reordering zones.

Where the ID fan sits

  1. Drying zones
  2. Zone exhaust hoods
  3. Exhaust duct
  4. Dust separator or scrubber
  5. Exhaust (ID) fan
  6. Stack

Exhaust fans sit on the roof or beside the redryer and pull from hoods over the drying and reordering zones, often through a cyclone, a dust separator or a wet scrubber. The amount exhausted is set by the humidity the zones must hold: too little and the leaf leaves wet, too much and heat is wasted. The suction is low, typically 50 to 150 mmWC including any separator.

Gas at the ID fan

Air temperature, normal50 to 80°C from the drying zones
Maximum or upsetAbout 100°C if the line stops with the steam coils on
Dust at the fanFine tobacco dust and fibre; heavier where no separator is fitted
Moisture and dew pointHumid air; saturated from the reordering zone, with condensate in the ducts
OtherTobacco dust is combustible and deposits can smoulder on hot surfaces
Density at the design temperatureAbout 1.03 kg/m³ at 70°C, 86% of standard air. Pressure developed and power drawn scale with density, so the fan is selected at this condition and the motor is checked at the coldest operating or start-up condition.

ID Fan selection for tobacco redrying plants

Blade formBackward inclined flat blade, plain and easy to clean
Material of constructionMild steel with a coating for drying zones; SS 304 for the reordering zone exhaust
Drive and arrangementBelt driven or direct coupled with a variable speed drive
Bearings and coolingBearings outside the air stream; no cooling needed
Flow controlVariable speed drive or damper on zone humidity
Also specifiedCasing drain, cleaning door and earthing

What this ID fan has to cope with

Dust and nicotine deposits

Fine tobacco dust in warm humid air sticks to blades and the casing, and with time forms a brown, tarry layer that throws the wheel out of balance. A simple blade shape, a separator ahead of the fan and cleaning during the off-season overhaul are the remedy.

Wet exhaust from reordering

The reordering zone exhaust is near saturation and condenses in the duct and the fan, washing dust into a wet paste and corroding mild steel. A stainless fan or casing, a falling duct with drains and a separate fan for this zone keep the problem away from the drying exhausts.

Fire risk

Tobacco dust deposits on steam coils and in exhaust ducts can smoulder. The exhaust fan is earthed, has no rubbing contact, and is included in the plant's fire detection and cleaning routine.

Energy and control

Redrying plants run hard through the buying season, usually two or three shifts, and then stand idle. Exhaust air carries most of the heat lost from the redryer, so controlling the exhaust fan on zone humidity instead of a fixed damper saves steam as well as fan power. Heat recovery from the exhaust to the incoming fresh air is worth assessing on large lines.

ID fan and FD fan in tobacco redrying plants

ID fanFD fan
PositionOn the zone exhaust hoodsBeside each zone, before the steam coils
What it handlesHumid air with tobacco dustRecirculated warm zone air
Temperature at the fan50 to 80°C50 to 90°C
Main design concernDeposits, condensation and fire riskEven flow through the leaf bed
ControlZone humidityZone air flow

See also the Forced Draft (FD) Fan for tobacco redrying plants.

Questions buyers ask

How many exhaust fans does a tobacco redryer have?

Usually one exhaust fan for a group of drying zones and a separate one for the reordering zone, though some lines exhaust each zone separately. The number depends on the redryer length, zone layout and how independently the zones are controlled.

Why is the reordering exhaust fan made of stainless steel?

The reordering zone adds steam and water to the leaf, so its exhaust is almost saturated and condenses in the duct and fan. Stainless steel resists the wet corrosion and the dust paste that forms, which would quickly attack mild steel.

Does the exhaust fan control the redryer moisture?

Indirectly. The exhaust rate sets how much moist air leaves each zone and so the humidity of the drying air. Controlling the exhaust fan on zone humidity helps hold the leaf moisture at the redryer exit.

Information needed to quote an ID fan for tobacco redrying plants

  1. Duty point. Gas volume in m³/h or Am³/h at the fan inlet and the static pressure the fan must develop, with the margin you want on each.
  2. Gas condition. Normal and maximum gas temperature at the fan, dust loading after the collector, moisture and any acid gases such as SO₂ or HCl.
  3. System. Boiler or furnace capacity and fuel, collector type and its pressure drop, and the existing fan curve or nameplate if this is a replacement.
  4. Mechanical. Drive arrangement, flow control (damper, inlet vanes or variable speed drive), rotation and discharge orientation, and a layout drawing or site photograph.
  5. Zone layout. Number of drying, cooling and reordering zones and which are served by this fan.
  6. Separator. Cyclone, dust separator or scrubber before the fan and its pressure drop.

Built and tested in Chennai

Adroit Fantech Engineers has designed and manufactured industrial fans at Ayanambakkam, Chennai since 2004. Each impeller, casing and shaft is built for the gas and temperature it will see, performance tested as per IS 4894 or BS 848 Part I, and balanced to grade G 6.3 or G 2.5 as per ISO 21940-11, with the records supplied with the fan. We also replace rotors and retrofit existing fans of any make.

ID Fan for related applications

Industries

Services on this fan

ID Fan for tobacco redrying plants: send us your duty point

Flow, pressure, gas temperature and the fuel are enough to start a selection.

Get a quote