Induced Draft (ID) Fan · designed and built in Chennai

Induced Draft (ID) Fan for Aluminium Holding Furnaces

The ID fan on an aluminium holding furnace removes a small, hot flue gas stream, usually with dilution air, and holds the furnace at a steady, slight pressure so that the metal surface stays protected. Precise pressure control at very low firing rates, not size, decides the design.

Send your duty pointCall +91 91766 67102
250 to 350°C after dilutionGas temperature, normal
0.62 kg/m³Gas density at 300°C
Backward curvedBlade form

How aluminium holding furnaces work

Holding furnaces keep molten aluminium at 680 to 760°C for die casting, gravity casting or a billet or slab caster. They are reverberatory, crucible or tower-type units fired by gas or oil, or electrically heated with radiant elements. Firing rates are low compared with a melter, since the furnace only makes up heat loss and the heat of small additions, and the burner spends much of the time on low fire. Flue gas leaves at 800 to 1,000°C in small volume. On many installations it goes to a stack on natural draft; where furnaces share a common flue, a recuperator is fitted, or degassing and fluxing fume must be captured, an ID fan with dilution air is used.

Where the ID fan sits

  1. Holding chamber
  2. Flue outlet
  3. Dilution air inlet
  4. Recuperator or common flue (if fitted)
  5. ID fan
  6. Stack

The fan sits after a dilution air inlet that cools the gas to a temperature suited to mild steel, or after a recuperator. In die-casting shops, several holding furnaces often share one flue and fan, each with its own damper. Suction is low, typically 30 to 100 mmWC, but must be finely controlled, since holding furnaces have small doors and ladling wells that leak easily.

Gas at the ID fan

Gas temperature, normal250 to 350°C after dilution
Maximum or upsetUp to 450°C if dilution air fails
Dust at the fanLow; alumina and flux traces
Moisture and dew pointCombustion moisture; well above dew point
Corrosive speciesMinor; chlorides from fluxing or degassing salts if used
Density at the design temperatureAbout 0.62 kg/m³ at 300°C, 52% of standard air. Pressure developed and power drawn scale with density, so the fan is selected at this condition and the motor is checked at the coldest operating or start-up condition.

ID Fan selection for aluminium holding furnaces

Blade formBackward curved, small and efficient at low flow
Material of constructionMild steel or boiler quality plate; heat-resisting steel impeller if dilution cannot be guaranteed
Drive and arrangementDirect coupled, arrangement 8 or 4 for small fans
Bearings and coolingShaft cooling disc and heat shield
Flow controlVariable speed drive on furnace pressure, with dilution air damper on temperature
Also specifiedInsulated casing and individual furnace dampers on a common flue

What this ID fan has to cope with

Over-draft and metal oxidation

Holding furnaces have a large open metal surface and frequent door openings. Too much draft pulls cold air in over the bath, cooling it and forming more dross. A fan selected for the actual small gas flow, with speed control on furnace pressure, avoids the over-draft common with oversized fans.

Common flue imbalance

When several furnaces share one fan, a furnace that opens its door or goes to high fire disturbs the draft at the others. Individual furnace pressure dampers, and a fan holding constant suction in the common flue, keep each furnace stable. The fan curve should be flat enough near the duty point that one furnace changing its demand does not shift the suction for the rest.

Dilution air failure

If the dilution damper sticks closed, the gas reaching the fan can exceed 400°C. Mild steel loses strength rapidly at that temperature. A high temperature interlock and an impeller rated for the upset temperature protect the fan. A dilution damper that fails open, rather than closed, is a simple further safeguard worth specifying on new systems.

Energy and control

Holding furnaces run continuously but at low fire for most of their time. A small, correctly sized fan on a variable speed drive uses little power, while an oversized fan throttled hard wastes it. Holding furnace energy is dominated by fuel; reducing air ingress through correct pressure control and tight doors saves more than the fan itself.

ID fan and FD fan in aluminium holding furnaces

ID fanFD fan
PositionAfter dilution or recuperator, before the stackOn or beside the furnace, feeding the burner
What it handlesSmall volume of diluted hot flue gasAmbient air
Temperature at the fan250 to 350°CAmbient, often warm
Main design concernFine pressure control to limit drossStable air at low fire
ControlFurnace pressureMetal temperature through burner ratio

See also the Forced Draft (FD) Fan for aluminium holding furnaces.

Questions buyers ask

Does an aluminium holding furnace need an ID fan?

Not always. A single holding furnace with a short flue often works on natural draft. An ID fan is used when several furnaces share a common flue, a recuperator adds resistance, or fume must be drawn to a filter. It then gives steadier pressure control than a stack damper alone.

Why does my holding furnace make so much dross?

One common cause is too much draft. If the ID fan or stack pulls cold air in through doors and ladling wells, the air oxidises the metal surface and forms dross. Holding the furnace at a slight positive pressure with a correctly sized, speed-controlled fan reduces this.

What temperature does a holding furnace ID fan see?

The flue gas leaves the holding chamber at 800 to 1,000°C, but it is small in volume and is usually cooled with dilution air to 250 to 350°C before the fan. The fan is checked for the upset temperature if dilution fails. The upset is usually short, so heat-resisting steel is needed only where dilution cannot be relied on.

Information needed to quote an ID fan for aluminium holding furnaces

  1. Duty point. Gas volume in m³/h or Am³/h at the fan inlet and the static pressure the fan must develop, with the margin you want on each.
  2. Gas condition. Normal and maximum gas temperature at the fan, dust loading after the collector, moisture and any acid gases such as SO₂ or HCl.
  3. System. Boiler or furnace capacity and fuel, collector type and its pressure drop, and the existing fan curve or nameplate if this is a replacement.
  4. Mechanical. Drive arrangement, flow control (damper, inlet vanes or variable speed drive), rotation and discharge orientation, and a layout drawing or site photograph.
  5. Number of furnaces. Number of holding furnaces on the flue, their firing rates and door arrangements.
  6. Pressure control. Required furnace pressure and the present control method.

Built and tested in Chennai

Adroit Fantech Engineers has designed and manufactured industrial fans at Ayanambakkam, Chennai since 2004. Each impeller, casing and shaft is built for the gas and temperature it will see, performance tested as per IS 4894 or BS 848 Part I, and balanced to grade G 6.3 or G 2.5 as per ISO 21940-11, with the records supplied with the fan. We also replace rotors and retrofit existing fans of any make.

ID Fan for related applications

Industries

Services on this fan

ID Fan for aluminium holding furnaces: send us your duty point

Flow, pressure, gas temperature and the fuel are enough to start a selection.

Get a quote