Forced Draft (FD) Fan for Tunnel Baking Ovens

The FD fan on a tunnel baking oven is the combustion air fan of each zone burner. It supplies air to the burner firing into the combustion chamber of the indirect heating circuit. It handles clean air, and what matters is a steady air-fuel ratio as the burner modulates to hold zone temperature for each product.

Send your duty pointCall +91 91766 67102
Hall air beside the oven, 30 to 50°CAir temperature at the fan
1.11 kg/m³Air density at 45°C
Backward curvedBlade form

How tunnel baking ovens work

A tunnel baking oven carries bread, buns, cakes or rusk on a steel band, mesh belt or tray conveyor through a series of zones, each held at its own temperature, typically 180 to 280°C. Many bread ovens are indirectly fired: a gas or oil burner fires into a combustion chamber, and the hot combustion gas, at about 400 to 600°C, is circulated by a recirculation fan through radiator tubes running above and below the band. The product never touches the flue gas. A small part of the circulating gas is bled off continuously by a flue exhaust fan and replaced by fresh combustion products. Separately, vapour extraction ducts with dampers remove the steam released by the dough from the baking chamber.

Where the FD fan sits

  1. Inlet filter
  2. FD fan
  3. Air damper
  4. Zone burner
  5. Combustion chamber
  6. Radiator circuit

Most zone burners are packaged with their own combustion air fan, mounted at the burner head on the side of the oven. Larger ovens sometimes use a central combustion air fan feeding a manifold with a damper at each burner. Either way the fan draws air from the bakery hall or from outside and pushes it through the burner against the pressure of the combustion chamber, typically 100 to 250 mmWC at full fire.

Air at the FD fan

Air temperature at the fanHall air beside the oven, 30 to 50°C
DustFlour dust in the bakery air; a fine inlet filter is needed
Pressure at the fan outletTypically 100 to 250 mmWC at the burner
TurndownBurners modulate with production rate and zone set points
Density at the design temperatureAbout 1.11 kg/m³ at 45°C, 93% of standard air. Pressure developed and power drawn scale with density, so the fan is selected at this condition and the motor is checked at the coldest operating or start-up condition.

FD Fan selection for tunnel baking ovens

Blade formBackward curved, quiet and stable on clean air
Material of constructionMild steel, painted; stainless steel where hygiene rules require
Drive and arrangementDirect mounted on the motor shaft
Bearings and coolingMotor bearings; fan kept clear of oven casing heat
Flow controlCharacterised damper linked to the fuel valve, or variable speed drive
Also specifiedInlet filter against flour dust, air pressure switch and inlet silencer

What this FD fan has to cope with

Flour dust on the impeller and burner head

Bakery air carries flour that settles on the blades and inside the burner head, slowly cutting air flow and upsetting fan balance. An inlet filter rated for fine dust, an air intake from a clean location away from mixers and dividers, and periodic cleaning keep the fan and burner right.

Hot hall air reducing capacity

Air beside the oven can reach 45 to 50°C, which lowers its density and the mass of oxygen the fan delivers. A fan sized on hall temperature at full fire, or ducted from outside the building, avoids burners running short of air on summer afternoons.

Noise in the production hall

A row of burner fans along the oven adds to the noise in a hall where people work all shift. Backward curved fans at moderate speed with inlet silencers, or a central fan in a plant room feeding a manifold, bring noise down. Flexible connections stop fan vibration travelling into the oven frame.

Energy and control

Burner air fans run whenever the oven is hot, including through product changeovers and idle periods. A burner with good turndown, and a fan whose air delivery follows the fuel through a linked damper or speed control, avoids heating surplus air. Checking flue oxygen at each zone at commissioning and after burner maintenance keeps gas use down.

ID fan and FD fan in tunnel baking ovens

ID fanFD fan
PositionOven roof, on the flue bleed to the stackAt each zone burner
What it handlesCombustion gas from the radiator circuitClean hall or outside air
Temperature at the fan250 to 350°C, up to 450°C upset30 to 50°C
Main design concernKeeping the circuit under suctionSteady air-fuel ratio
ControlCircuit suction and burner firingBurner modulation

See also the Induced Draft (ID) Fan for tunnel baking ovens.

Questions buyers ask

What does the FD fan do on a bakery tunnel oven?

It is the combustion air fan of the zone burner. It supplies air so the burner can fire into the combustion chamber that heats the radiator tubes. Each zone usually has its own burner and fan, so the duty is small, but the forced draft fan must hold a steady air-fuel ratio as the burner modulates.

Why does the tunnel oven burner trip on low air pressure?

Common causes are a clogged inlet filter, flour dust on the impeller, a fan drawing very hot air from beside the oven, or a slipping belt on older units. Each reduces air pressure at the burner until the safety switch opens. Cleaning the filter and fan, and checking the fan curve against the burner requirement, usually cures it.

Can one combustion air fan serve all burners of a baking oven?

Yes. A central fan with a manifold and a damper at each burner is used on large ovens and is quieter and easier to maintain than many small fans. The manifold must be sized so each burner still gets enough pressure at full fire, and the fan needs a stable curve as burners modulate independently.

Information needed to quote an FD fan for tunnel baking ovens

  1. Duty point. Combustion air quantity in m³/h or kg/h and the static pressure at the fan outlet, with the margins you want.
  2. Air condition. Site ambient temperature range and altitude, and whether the fan takes ambient air or air already heated.
  3. System. Boiler or furnace capacity and fuel, resistance of the air heater, windbox, grate or burner, and the existing fan curve or nameplate if this is a replacement.
  4. Mechanical. Drive arrangement, flow control (damper, inlet vanes or variable speed drive), noise limit, rotation and discharge orientation.
  5. Burners. Number of burners, rating of each and the air pressure each needs at full fire.
  6. Air source. Whether air is drawn from the bakery hall or ducted from outside, and the hall temperature near the oven.

Built and tested in Chennai

Adroit Fantech Engineers has designed and manufactured industrial fans at Ayanambakkam, Chennai since 2004. Each impeller, casing and shaft is built for the gas and temperature it will see, performance tested as per IS 4894 or BS 848 Part I, and balanced to grade G 6.3 or G 2.5 as per ISO 21940-11, with the records supplied with the fan. We also replace rotors and retrofit existing fans of any make.

FD Fan for related applications

Industries

Services on this fan

FD Fan for tunnel baking ovens: send us your duty point

Flow, pressure, air temperature and the fuel are enough to start a selection.

Get a quote