13, Galaxy Road, Ponniamman Nagar, Ayanambakkam, Chennai 600 095 +91 91766 67102  |  +91 91766 67103  |  marketing@adroitfantech.com
Home › Applications › ID Fan › Palm Fibre and Shell Fired Boilers

Induced Draft (ID) Fan · designed and built in Chennai

Induced Draft (ID) Fan for Palm Fibre and Shell Fired Boilers

On a palm fibre and shell fired boiler the ID fan has to follow steam demand that swings with batch sterilisation, and handle gas carrying fibre ash and hard shell grit. Erosion from the shell, and recovering draft quickly every time a steriliser opens its steam valve, decide the design of this induced draft fan.

Send your duty pointCall +91 91766 67102
180 to 230°C at the fanGas temperature, normal
0.75 kg/m³Gas density at 200°C
Radial tipped where the fan follows a multicloneBlade form

How palm fibre and shell fired boilers work

Palm oil mills burn their own mesocarp fibre and kernel shell to raise steam for the sterilisers, digesters and back-pressure turbine. Fibre leaves the press at 35 to 45% moisture, with 5 to 8% ash and a calorific value of about 2,600 to 3,000 kcal/kg as fired; shell is drier and denser at about 4,000 kcal/kg with 2 to 4% ash. They are fired together, typically about 70 parts fibre to 30 parts shell, on fixed or reciprocating grates in water tube boilers of 10 to 45 TPH. Fibre burns largely in suspension, shell on the grate. Gas passes the boiler bank, economiser or air heater where fitted, a multiclone and a wet scrubber, ESP or bag filter, then the ID fan. Steam demand swings with batch sterilisation cycles.

Where the ID fan sits

  1. Grate furnace
  2. Boiler bank
  3. Economiser or air heater
  4. Multiclone
  5. Scrubber, ESP or bag filter
  6. ID fan
  7. Chimney

The fan is after the multiclone and final collector. Many older mills used a multiclone only, and the fan then sees fibre ash and fine shell grit at several grams per cubic metre; newer mills add a wet scrubber, ESP or bag filter to meet emission limits. Suction at the fan inlet is typically 150 to 250 mmWC. The fan usually stands outdoors near the chimney in a hot, humid climate.

Gas at the ID fan

Gas temperature, normal180 to 230°C at the fan
Maximum or upsetAround 280°C at peak firing with fouled surfaces
Dust at the fanFibre ash with hard shell grit; several g/Nm³ after a multiclone only
Moisture and dew pointWet fibre gives a water dew point of about 55 to 60°C
Corrosive speciesPotassium and chlorides in the ash; low sulphur
Density at the design temperatureAbout 0.75 kg/m³ at 200°C, 63% of standard air. Pressure developed and power drawn scale with density, so the fan is selected at this condition and the motor is checked at the coldest operating or start-up condition.

ID Fan selection for palm fibre and shell fired boilers

Blade formRadial tipped where the fan follows a multiclone; backward curved with liners after a filter or ESP
Material of constructionMild steel casing; wear-resistant plate on the blades and at the scroll cut-off
Drive and arrangementDirect coupled, arrangement 8, at moderate tip speed
Bearings and coolingPedestal bearings with a shaft cooling disc
Flow controlVariable speed drive on a fast furnace draft loop
Also specifiedBolted liners, an inspection door, weatherproof motor and terminal box

What this ID fan has to cope with

Shell grit erosion

Kernel shell is hard, and fragments that escape the grate are as abrasive as sand. Where the fan follows only a multiclone, the leading edges and the outer part of the blades wear quickly. Wear-resistant plate, replaceable liners and a lower tip speed extend impeller life, and an efficient final collector removes most of the problem.

Load swings from sterilisers

When a batch steriliser opens, steam demand jumps, the firing rate rises and the gas volume follows within a minute or two. A fan on a slow damper lets the furnace go positive and blow ash out of the doors. A variable speed drive on a fast draft loop keeps the furnace under suction through each cycle.

Fan sized before mill expansion

Mills raise their throughput over the years, and boilers are pushed beyond their original rating with more fibre. The ID fan becomes the bottleneck. Measured gas volume and suction at today's peak, rather than the original nameplate, form the basis for an uprated impeller or a new fan.

Energy and control

A palm oil mill runs in step with fruit arrival, with long days in peak crop and short weeks in the lean months. Steam demand cycles with the sterilisers within each hour. A variable speed drive handles both the hourly swings and the seasonal drop, and saves the power a throttled damper would waste. Reducing air ingress at the furnace doors and ash hoppers also lowers the gas the fan must move.

ID fan and FD fan in palm fibre and shell fired boilers

ID fanFD fan
PositionAfter the multiclone and final collectorBeside the furnace, under the grate
What it handlesFlue gas with fibre ash and shell gritAmbient humid air
Temperature at the fan180 to 230°CAmbient, 25 to 38°C
Main design concernShell grit erosion and fast draft responseFollowing steriliser load swings
ControlFast furnace draft loopSteam pressure with secondary air

See also the Forced Draft (FD) Fan for palm fibre and shell fired boilers.

Questions buyers ask

Why does the ID fan wear fast on a palm oil mill boiler?

Kernel shell fragments and fibre ash are abrasive, and many mill boilers have only a multiclone ahead of the fan. The grit erodes the blade leading edges and scroll. Wear plate, liners, lower tip speed and a better final collector all extend impeller life between repairs.

How does the ID fan cope with steriliser steam swings?

Each steriliser cycle changes steam demand quickly, and the furnace firing follows. A variable speed drive with a fast furnace draft loop changes fan speed within seconds and keeps the furnace under suction. A damper on a slow actuator often cannot keep up, and the furnace goes positive.

Can the ID fan be uprated for a higher mill throughput?

Often, yes. A new impeller of larger diameter or different blade form on the existing casing, sometimes with a larger motor, can give more volume and suction. The duty should be based on measured gas flow and suction at the present peak, and the shaft, bearings and foundation checked for the new load.

Information needed to quote an ID fan for palm fibre and shell fired boilers

  1. Duty point. Gas volume in m³/h or Am³/h at the fan inlet and the static pressure the fan must develop, with the margin you want on each.
  2. Gas condition. Normal and maximum gas temperature at the fan, dust loading after the collector, moisture and any acid gases such as SO₂ or HCl.
  3. System. Boiler or furnace capacity and fuel, collector type and its pressure drop, and the existing fan curve or nameplate if this is a replacement.
  4. Mechanical. Drive arrangement, flow control (damper, inlet vanes or variable speed drive), rotation and discharge orientation, and a layout drawing or site photograph.
  5. Fuel ratio. Proportion of fibre and shell fired, and any empty fruit bunch added.
  6. Load cycle. Number of sterilisers and the steam swing during a cycle.

Built and tested in Chennai

Adroit Fantech Engineers has designed and manufactured industrial fans at Ayanambakkam, Chennai since 2004. Each impeller, casing and shaft is built for the gas and temperature it will see, performance tested as per IS 4894 or BS 848 Part I, and balanced to grade G 6.3 or G 2.5 as per ISO 21940-11, with the records supplied with the fan. We also replace rotors and retrofit existing fans of any make.

ID Fan for related applications

Industries

Services on this fan

ID Fan for palm fibre and shell fired boilers: send us your duty point

Flow, pressure, gas temperature and the fuel are enough to start a selection.

Get a quote