Induced Draft (ID) Fan for Arecanut Husk Fired Boilers

The ID fan on an arecanut husk fired boiler must cope with fuel moisture that changes through the year, from wet fresh husk in the harvest to dry stored husk later. Wet husk can raise the flue gas volume per tonne of steam by a third or more, so the fan's volume range, not its pressure, decides the design.

Send your duty pointCall +91 91766 67102
170 to 220°C, often with no economiserGas temperature, normal
0.75 kg/m³Gas density at 200°C
Backward curvedBlade form

How Arecanut husk fired boilers work

Arecanut husk is the fibrous outer layer of the areca fruit, removed when the nut is dehusked, mainly in Karnataka, Kerala and Assam. Fresh husk carries 40 to 60% moisture; sun-dried husk falls to 15 to 25%. Ash is low, typically 2 to 5%, and dried husk has a calorific value of about 3,500 to 4,000 kcal/kg. The husk is coarse, fibrous and springy, so it bridges in hoppers and packs unevenly on the grate. It is fired on fixed or inclined grates of smoke tube and small water tube boilers in areca processing and food plants, often blended with firewood or coconut shell. The flue gas passes the boiler and a cyclone or multicyclone before the ID fan.

Where the ID fan sits

  1. Fixed or inclined grate
  2. Boiler passes
  3. Cyclone or multicyclone
  4. ID fan
  5. Chimney

The fan sits after the cyclone, typically on boilers of 1 to 5 TPH. Ash is low, but fibrous flakes of half-burnt husk are carried from the furnace to the cyclone, and some pass through. Suction at the fan is typically 80 to 160 mmWC. Because the gas volume follows the fuel moisture, a fan sized for dry husk runs short in the harvest season, and one sized for wet husk runs far back on its curve for the rest of the year.

Gas at the ID fan

Gas temperature, normal170 to 220°C, often with no economiser
Maximum or upsetUp to 260°C with dry husk and fouled tubes
Dust at the fanLow ash, with fibrous char flakes after a cyclone
Moisture and dew pointWater dew point about 50 to 65°C, at the top of the range with fresh husk
Corrosive speciesMinor
Density at the design temperatureAbout 0.75 kg/m³ at 200°C, 63% of standard air. Pressure developed and power drawn scale with density, so the fan is selected at this condition and the motor is checked at the coldest operating or start-up condition.

ID Fan selection for Arecanut husk fired boilers

Blade formBackward curved, selected to stay efficient over a wide flow range
Material of constructionMild steel throughout
Drive and arrangementDirect coupled arrangement 8, or belt driven on small units
Bearings and coolingPedestal bearings with a cooling disc
Flow controlVariable speed drive on furnace draft
Also specifiedCasing drain, inspection door, and insulation where wet husk lowers the gas temperature

What this ID fan has to cope with

Seasonal change in gas volume

Fresh husk in the harvest months carries far more water than stored husk, and the extra vapour raises the gas volume by a third or more for the same steam. A fan selected at the wet-husk point, with a variable speed drive, covers both seasons; a fixed-speed fan with a damper wastes power for most of the year or starves the boiler in the harvest.

Bridging and uneven firing

Springy husk bridges in the hopper and then drops in a mass. The bed starves, then floods, and the gas volume swings with it. A responsive draft loop on the ID fan keeps the furnace at suction through these swings, while hopper agitators or a wider throat reduce how often they happen.

Condensation with wet husk

Wet husk cools the furnace and raises the dew point of the gas. At low load the gas at the fan can approach condensation, and the fine ash in the casing turns to a paste that dries hard. Casing insulation, a drain, and a minimum firing rate when burning fresh husk prevent these deposits.

Energy and control

Areca processing is seasonal, with the heaviest steam demand in the harvest months when husk is wettest. For the rest of the year the boiler runs on drier husk, often at lower load. A variable speed drive suits this pattern: the fan runs fast only when wet husk needs it. Drying husk in the sun, or with flue gas, cuts fan power and raises boiler output at the same time.

ID fan and FD fan in Arecanut husk fired boilers

ID fanFD fan
PositionAfter the cyclone, before the chimneyAt the boiler front, feeding the grate
What it handlesFlue gas with fibrous char flakesAmbient air
Temperature at the fan170 to 220°C, up to 260°CAmbient, 20 to 40°C
Main design concernSeasonal gas volume rangePressure through an uneven bed
ControlFurnace draftSteam pressure

See also the Forced Draft (FD) Fan for Arecanut husk fired boilers.

Questions buyers ask

Why does my arecanut husk boiler struggle in the harvest season?

Fresh husk is wet, so the flue gas volume rises and the furnace runs cooler. If the ID fan was sized for dry husk, it cannot move the extra gas and the boiler loses output. An induced draft fan sized for wet husk, with a variable speed drive, covers both seasons without wasting power.

Can arecanut husk be fired with firewood?

Yes, and many plants blend husk with firewood or coconut shell to steady the fire. Blending changes the gas volume and temperature at the fan, so the ID fan should be checked at the wettest blend the plant expects to fire, usually fresh husk with little wood during the harvest.

What dust collector is used before the ID fan on an arecanut husk boiler?

Usually a cyclone or multicyclone on smaller boilers, with a bag filter where emission limits require it. Husk ash is low, but fibrous char flakes escape the furnace, so a collector protects the fan from build-up and cuts visible emission from the chimney. The collector's pressure drop is part of the fan duty.

Information needed to quote an ID fan for Arecanut husk fired boilers

  1. Duty point. Gas volume in m³/h or Am³/h at the fan inlet and the static pressure the fan must develop, with the margin you want on each.
  2. Gas condition. Normal and maximum gas temperature at the fan, dust loading after the collector, moisture and any acid gases such as SO₂ or HCl.
  3. System. Boiler or furnace capacity and fuel, collector type and its pressure drop, and the existing fan curve or nameplate if this is a replacement.
  4. Mechanical. Drive arrangement, flow control (damper, inlet vanes or variable speed drive), rotation and discharge orientation, and a layout drawing or site photograph.
  5. Fuel moisture range. Moisture of fresh and stored husk, and any blend with wood or shell.
  6. Season profile. Steam demand in the harvest and off-season months.

Built and tested in Chennai

Adroit Fantech Engineers has designed and manufactured industrial fans at Ayanambakkam, Chennai since 2004. Each impeller, casing and shaft is built for the gas and temperature it will see, performance tested as per IS 4894 or BS 848 Part I, and balanced to grade G 6.3 or G 2.5 as per ISO 21940-11, with the records supplied with the fan. We also replace rotors and retrofit existing fans of any make.

ID Fan for related applications

Industries

Services on this fan

ID Fan for Arecanut husk fired boilers: send us your duty point

Flow, pressure, gas temperature and the fuel are enough to start a selection.

Get a quote