Forced Draft (FD) Fan · designed and built in Chennai

Forced Draft (FD) Fan for LSHS Fired Boilers

The FD fan on an LSHS fired boiler is the forced draft fan that supplies combustion air through the air heater to the burners. It handles ambient air, but LSHS needs warm, well-mixed air to burn its waxy residue cleanly, so steady air flow at low fire and reliable air preheating are what matter.

Send your duty pointCall +91 91766 67102
Ambient, 25 to 45°CAir temperature at the fan
1.13 kg/m³Air density at 40°C
Backward curvedBlade form

How LSHS fired boilers work

LSHS, low sulphur heavy stock, is a waxy residual fuel with a pour point typically 40 to 60°C, a calorific value near 10,000 kcal/kg and sulphur usually below 1%. It must be kept heated in tanks and lines and raised to about 120 to 140°C for atomisation. It is fired in shell boilers and in water tube boilers of 10 to 60 TPH in chemical, pharmaceutical and fertiliser plants. On the larger units the gas passes the boiler bank, economiser and often a tubular air heater before an ID fan and the stack, while the FD fan feeds the burners through the air heater. Lower sulphur than furnace oil allows a cooler stack and more heat recovery.

Where the FD fan sits

  1. Air intake
  2. FD fan
  3. Steam coil air preheater
  4. Tubular air heater
  5. Windbox
  6. Burners

The FD fan stands near the air heater and pushes ambient air through a steam coil air preheater, used at start-up and low load, then through the tubular air heater to the windbox. Preheating the air helps LSHS burn out at low fire and keeps the air heater cold end above dew point. The fan works against the preheaters, ducts, windbox and burner registers, typically 150 to 250 mmWC on balanced draft units of this size.

Air at the FD fan

Air temperature at the fanAmbient, 25 to 45°C
Air after the air heater180 to 250°C, downstream of the fan
Pressure at the fan outletTypically 150 to 250 mmWC
DustClean air
Excess airAbout 15 to 20% at full load, higher at low fire
Density at the design temperatureAbout 1.13 kg/m³ at 40°C, 94% of standard air. Pressure developed and power drawn scale with density, so the fan is selected at this condition and the motor is checked at the coldest operating or start-up condition.

FD Fan selection for LSHS fired boilers

Blade formBackward curved, giving a stable curve at low flow
Material of constructionMild steel
Drive and arrangementDirect coupled
Bearings and coolingPedestal bearings; no cooling needed
Flow controlVFD with O₂ trim on total air
Also specifiedInlet silencer, air flow element in the cold air duct

What this FD fan has to cope with

Poor burnout at low fire

At low fire the air velocity through the register falls, mixing weakens and LSHS leaves unburnt carbon. A fan that cannot control steadily at low flow makes this worse. Sizing the fan for the real duty rather than throttling a large margin, and setting a minimum air flow in the control, keep low-fire combustion clean.

Steam coil preheater out of service

When the steam coil preheater fails or is bypassed, cold air reaches the tubular air heater, its cold end corrodes and starts to leak air into the gas side. The FD fan then carries more air for the same combustion. Keeping the steam coil in service at start-up and low load protects both heaters and the fan duty.

Oversized fan after a fuel change

Boilers converted to LSHS from furnace oil or coal often keep their original FD fan, sized for a different air requirement and resistance. The fan runs throttled, wastes power and gives poor control at low fire. A new impeller or a VFD sized for the LSHS duty corrects both the power and the control.

Energy and control

Most LSHS boilers run continuously at 50 to 90% load. A VFD on the FD fan with O₂ trim holds excess air at about 3 to 4% O₂ across this range and saves more energy than damper control. Because LSHS is a costly fuel, the larger saving comes through the fuel bill: every point of excess air removed reduces both fan power and stack loss.

ID fan and FD fan in LSHS fired boilers

ID fanFD fan
PositionAfter the air heater, before the stackAhead of the steam coil and tubular air heater
What it handlesFlue gas with occasional oily carbonAmbient air
Temperature at the fan150 to 180°CAmbient, 25 to 45°C
Main design concernDeposits and acid dew pointSteady low-fire air for burnout
ControlFurnace draftFiring rate and oxygen

See also the Induced Draft (ID) Fan for LSHS fired boilers.

Questions buyers ask

Why does an LSHS boiler need a steam coil air preheater?

LSHS burns better with warm combustion air, and the tubular air heater corrodes if it receives cold air at start-up. The steam coil preheater warms the air from the FD fan before it reaches the main air heater, which protects the cold end and helps clean light-off. It is usually switched out once the boiler is at steady load.

What controls the FD fan on an LSHS fired boiler?

The fan speed or damper is set by the combustion control from the firing rate and trimmed by flue gas oxygen. On larger boilers the air flow is measured and kept in ratio with fuel flow, with cross-limits so that air leads fuel on a load increase and lags it on a decrease.

Can the same FD fan be used if the boiler changes from LSHS to natural gas?

Often yes, but the duty changes. Natural gas runs at lower excess air, and a low NOx gas burner may need more pressure at the register than the oil burner did. The fan curve should be checked against the new burner's air flow and pressure before the conversion is finalised.

Information needed to quote an FD fan for LSHS fired boilers

  1. Duty point. Combustion air quantity in m³/h or kg/h and the static pressure at the fan outlet, with the margins you want.
  2. Air condition. Site ambient temperature range and altitude, and whether the fan takes ambient air or air already heated.
  3. System. Boiler or furnace capacity and fuel, resistance of the air heater, windbox, grate or burner, and the existing fan curve or nameplate if this is a replacement.
  4. Mechanical. Drive arrangement, flow control (damper, inlet vanes or variable speed drive), noise limit, rotation and discharge orientation.
  5. Air preheating. Whether a steam coil and tubular air heater are fitted, and their air-side resistance.
  6. Burner data. Number of burners and register pressure at full fire.

Built and tested in Chennai

Adroit Fantech Engineers has designed and manufactured industrial fans at Ayanambakkam, Chennai since 2004. Each impeller, casing and shaft is built for the gas and temperature it will see, performance tested as per IS 4894 or BS 848 Part I, and balanced to grade G 6.3 or G 2.5 as per ISO 21940-11, with the records supplied with the fan. We also replace rotors and retrofit existing fans of any make.

FD Fan for related applications

Industries

Services on this fan

FD Fan for LSHS fired boilers: send us your duty point

Flow, pressure, air temperature and the fuel are enough to start a selection.